Precision Cable Manufacturing

Submersible Cables

High-performance submersible cables designed for irrigation pumps, water supply systems, and industrial pump installations, offering superior flexibility, durability, and reliable power transmission in underwater environments.

Submersible Flat Cable

Vita Cable PVC Insulated Submersible Flat Cables are specifically designed for submersible pump installations, deep well applications, and borewell motor wiring. The flat construction allows for easy winding and installation while providing superior moisture and abrasion resistance. Available in 3-core and 4-core configurations with rated voltage up to 1100V.

Key Features

Flat cable construction for easy installation in boreholes
High PVC insulation for moisture resistance
Suitable for submersible pump motor wiring
1100V rated voltage for high-capacity applications
Copper conductor (99.97% purity)
Available in 3-core and 4-core options
Cross-section range: 1.0 sqmm to 70 sqmm
BIS compliant & ISO certified manufacturing

2. Technical Specifications

2.1 Conductor Specifications

Parameter Specification Standard Reference
Conductor Material Electrolytic Grade Copper IS 694:2010
Conductor Type Stranded (Class 2) IS 694:2010
Copper Purity 99.97% minimum IS 694:2010
Cross-Section Range 1.0 sqmm to 70 sqmm ---
Number of Strands Size dependent IS 694:2010

2.2 Insulation Specifications

Parameter Specification Standard Reference
Insulation Material PVC (Polyvinyl Chloride) IS 694:2010
Insulation Color Black with core identification IS 694:2010
Core Configuration 3-Core or 4-Core Flat IS 694:2010
Operating Temperature -5°C to +60°C continuous IS 694:2010
Insulation Resistance ≥ MΩ/km at 20°C IS 694:2010

2.3 Voltage & Current Ratings (3-Core Configuration)

Cross-Section (sqmm) Rated Voltage Current Rating (Amps @ 60°C) Resistance (Ω/km)
1.0 1100V AC 10A 18.1
1.5 1100V AC 15A 12.1
2.5 1100V AC 20A 7.41
4.0 1100V AC 26A 4.62
6.0 1100V AC 34A 3.08
10 1100V AC 46A 1.83
16 1100V AC 61A 1.15
25 1100V AC 80A 0.727
35 1100V AC 106A 0.524
50 1100V AC 134A 0.387
70 1100V AC 171A 0.268

Note: Current ratings for 3-core are based on IS 694:2010 at ambient temperature of 30°C with 30°C rise, 4-core ratings are 5-10% lower due to increased core density.

2.4 Physical Specifications

Cable Construction Flat (3-core or 4-core)
Outer Width 12 mm (1.0-1.5 sqmm) to 45 mm (70 sqmm)
Outer Thickness 8 mm (1.0-1.5 sqmm) to 18 mm (70 sqmm)
Weight Range 3.5 kg/km (1.0 sqmm) to 200 kg/km (70 sqmm)
Minimum Bending Radius 4 x Outer Width (at -5°C)
Tensile Strength ≥5 MPa (insulation)
Elongation at Break ≥ 200% (insulation)

3. Standards & Certifications

  • IS 694:2010 - PVC insulated cables for rated voltages up to and including 450/750V
  • IS 8130 - Submersible motor cables (where applicable)
  • BIS Certified - Bureau of Indian Standards certification
  • ISO 9001:2015 - Quality Management System certified manufacturing

4. Applications

  • Submersible Pump Installations: Deep well and borewell motor wiring
  • Agricultural Applications: Farm pump installations, irrigation systems
  • Water Supply Systems: Municipal and industrial water supply
  • Underground Installations: Protected underground wiring
  • Wet Environments: Applications requiring moisture resistance

5. Installation Guidelines

  • Bending Radius: Do not exceed 4 x outer width of cable
  • Load Rating: Do not exceed current ratings specified in Section 2.3
  • Grounding: Ensure proper earthing for motor wiring
  • Storage: Store in cool, dry place away from sunlight (shelf life: 24 months)
  • Termination: Use appropriate lugs and connectors for conductor size
  • Protection: Protect from mechanical damage during installation